An irrigation operator selecting a block may need three answers. Was the request sent? Did the local controller accept it? Did water reach the block? ProSight projects can show each stage separately so the operator can see where a change stopped.

Define the supervisory command

List the action, the operator role allowed to request it, the controller that owns it, and the feedback that demonstrates the result. For a valve, specify the requested position, the controller response and a travel or flow indication. The PLC or irrigation controller retains local sequencing, interlocks and protective functions.

Choose the reply and expiry behaviour

ThingsBoard documents remote procedure calls (RPC) from dashboards, rule chains and APIs. A one-way call expects no reply. A two-way call waits for a device response within a timeout. Persistent requests can remain pending until their expiry. Decide whether a delayed request would still be appropriate after the field link returns. Commission the selected behaviour with the site team.

Show what actually happened

For a demonstration, present the operator request, device acknowledgement and measured outcome on one timeline. If the controller replies but flow does not change, the display should show the two observations separately. If the link drops, show the time of the last confirmed feedback.

Accept the workflow before handover

Review an accepted request, a refusal, an expired request and missing feedback in a site-approved simulator or test environment. Record the expected operator indication in each case. ProSight and the site owner confirm the device interface, permissions and licensed scope for the project.

Distinguish a device downlink from equipment feedback

ThingsEye documents downlink commands for supported devices. An equipment control project also needs a site-approved command, a named operator role, local controller authority and a measured outcome. A delivery acknowledgement alone cannot establish valve position or pump flow.