OPC UA integration for PLC and SCADA telemetry
A pump station can already show discharge pressure on its local HMI. With an approved OPC UA server and gateway, the same point can feed a ProSight trend at head office. Start with one pressure reading and one pump-running indication so operators can compare the analogue and status paths.
Map the plant point to the operator view
Identify the source server and namespace, the node identifier or browse path, data type, engineering unit and asset name. Record where the timestamp originates and how a poor-quality or stale value should appear. For the pump station, agree whether pressure is in kPa or bar and whether the running indication comes from actual drive feedback.
Choose a subscription or polling
ProSight is built on ThingsBoard. Its IoT Gateway OPC UA connector can subscribe to monitored nodes or poll for values. A changing pressure signal and an occasional change in pump state may need different update behaviour. Agree the acceptable delay with the operator and check the proposed load with the owner of the OPC UA server.
Witness a read-only pilot
Have the commissioning team compare the local display and ProSight at a known time. In an approved test environment, observe a communications interruption and recovery. Record the last good reading, how the dashboard marks its age, and when fresh values resume. Include the approved server access policy, gateway version and tag list in handover.
Scope any write-back separately
For a project that needs a supervisory command, identify the operator role, local permissives, request expiry and independent feedback point. The project team confirms the permitted operations for the installed server, gateway and controller.