top of page

BACnet integration for building management systems

3 days ago
1 min read

Two floors can both have a point called Zone temperature. To show the right reading in ProSight, the building controls contractor and facilities team need to agree which controller, object and property belong to each zone. Start with one occupied zone and its air handler.

Prepare the point schedule

For each selected point, record the building, floor, equipment label, device instance, object type and instance, property, expected unit and read permission. Distinguish a measured room temperature from its setpoint and a fan run indication from its start request.

Map the BACnet object to an operator display

ThingsBoard’s IoT Gateway BACnet connector documents mappings by object and property. For a ProSight project, agree which values belong in the time-series history and which describe the equipment. For example, trend the measured temperature while keeping the zone name beside it as context.

Witness one zone before adding more

At an agreed time, compare the local BMS reading and the ProSight display. Record both values, the engineering unit and the age of the last sample. In an approved test environment, check how a missing update appears and whether the display recovers when the feed returns.

Agree how control requests are handled

If the facilities team needs supervisory setpoint changes, record the allowed range, local override behaviour, responsible role and independent feedback. The project team confirms write permissions and the commissioning scope for that building.

Recent Posts

See All

Comments


prosight-software-logo (1).png