Tank and pump station monitoring
When a reservoir runs low, the useful question is whether the pump ran and whether water arrived. Put level, flow and pump feedback on the same timeline to give an operator a practical starting point.
Choose what the operator needs to see
For a tank, specify the measuring range, level units and reference point. For a pump station, add run feedback, a fault indication and a discharge measurement where available. Identify which values come from instruments and which come from a controller.
Check the measurement chain
A hydrostatic level transmitter is one option for a suitable liquid. Select the range and materials for the installation. Match the exact output variant to the logger or RTU input, record the scaling and compare the indicated level with a known site reference.
Test a loss of communications
A flat trend can mean that the level is steady or that the last reading is stale. Agree on the expected reporting interval and make the last update visible. During commissioning, test both a low-level event and a missing update using a controlled example.
Define the control boundary
A monitoring project can begin with read-only pump feedback. Specify any remote commands separately with the site controls team, including permissives, acknowledgement and commissioning.