Designing alarms, recovery and missing-data alerts
An alarm should tell an operator which condition occurred and what evidence to check. Specify when it opens, when it clears and who needs to know before enabling notifications.
Write the alarm in site terms
An example brief is “North tank level is below the agreed operating threshold for the agreed delay.” Record the signal, units, threshold, delay, severity, owner and expected operator action. Have operations approve the actual values.
Separate acknowledgement from recovery
Acknowledgement records that someone has seen the event. Recovery records that the underlying condition has returned to the agreed range. Specify what should happen if the signal repeatedly crosses the threshold or goes stale while the alarm is active.
Give loss of telemetry its own condition
A missing update provides evidence about communications, not the tank contents. Set the expected update interval and allowable delay. Define what an operator should see during an outage and when a fresh reading arrives.
Witness a complete event
Use authorised test data to record the trigger reading, event time, recipient receipt, acknowledgement where required, and recovery. Keep this operational notification workflow distinct from local protection and safety functions.