Field communications and gateway integration
Plan the connection from the measuring device to the ProSight dashboard. Device output, local network, gateway and site uplink are separate decisions. Confirm compatibility across that full path before ordering equipment.
Wired instruments and PLCs
Identify the exact model and interface. A 4–20 mA transmitter needs a compatible analogue input with agreed engineering-unit scaling. For Modbus RTU over RS-485, supply the manufacturer's register map, addressing conventions, data types and serial settings. For Ethernet devices, identify the application protocol as well as the physical connection.
LoRaWAN and cellular field sites
For a LoRaWAN sensor, identify its regional radio variant, payload decoder, network and gateway coverage. For a cellular site, confirm power, coverage and the reporting interval. Ask how the device behaves during an outage and how old data is identified when it arrives.
MQTT and gateway translation
If an integration uses MQTT, provide an example payload with the timestamp, device identity, value and units. Confirm the broker and gateway responsibilities with the integration team. Support for a protocol name alone does not establish compatibility with a particular device or payload.
Commission one measurement
Compare one known field reading with its displayed value and timestamp. Check a missing update and recovery. Capture the model, mapping and agreed test outcome before rolling the configuration out to other sites.